| Phone Us |
|
|||
| Return to Rectifiers Page | ||||
| INPUT | |
|---|---|
| Voltage | 208/220/240 VAC, single phase; operating range 176 to 264 VAC, no taps required. |
| Frequency | 45 to 65 Hz |
| Protection | 2-pole circuit breaker |
| OUTPUT | |
|---|---|
| Voltage |
Float voltage is adjustable from 48 to 60 volts DC Equalize voltage is adjustable from 48 to 60 volts DC |
| Current | Current limit: adjustable from 0 to 50 amps |
| Regulation | ± 0.5 percent for 0 to 100 percent load, within the specified input voltage and frequency range |
| Filtering |
Voice band - less than 32 dBmC Wide band noise - less than 350mV, peak-to-peak, over a 10Hz to 14mHz range |
| Protection | Circuit breaker |
| Over voltage shutdown | Adjustable up to 60 VDC |
| Turn-on | Soft start |
| Load current | Modules share within ± 10 percent from 10 to 100 percent rating |
| ENVIRONMENT | |
|---|---|
| Operating temperature | -40° F (-40° C) to +149° F (65° C) |
| Storage temperature | -58° F (-50° C) to +185° F (85° C) |
| Humidity | 0-95 percent relative humidity; non-condensing |
| Altitude | 0 to 7,000 feet (0 to 2,133 meters) |
| EMI | FCC Part 15, Subpart J for Class A equipment; VDE0875, Class N |
| Audible noise | Less than 55 dBA, five feet from any vertical surface |
| Module weight | 25 lbs (11.4 Kgs) |
| Module height | 12.25 inches (31.75cm) when mounted in shelf |
| Shelf depth | 14.5 inches (37cm) maximum |
|
MIP Inc, 1015 Elrod Road, Piedmont, South Carolina 29673
864-269-5895 - FAX 864-269-5898 After Hours Emergency Telephone Number - (864) 269-5895 , Ext 30
|